![]() | Tech Notes | ![]() ![]() | ||||
![]()
And More... | ||||||
| Technical Notes 7D Abstract: Moisture, formed by the condensation of water vapor, can cause many problems in brick masonry walls. Among these are: efflorescence, spalling, corrosion and interior finish damage. This Technical Notes outlines a method used by designers to assess the possibility of condensation occurring in a given wall section; and, describes how to alleviate condensation problems through the use of vapor barriers and/or ventilation. Key Words: brick, condensation, dew point, humidity, permeance, relative humidity, saturated vapor pressure, saturation, vapor barrier, vapor pressure, vapor resistance, walls. INTRODUCTION When a vapor pressure differential exists, water vapor will move independently of air. The vapor movement through common building materials is at a relatively high rate for common pressure differentials. When vapor passes through pores of homogenous walls, which are warm on one side and cold on the other, it may reach its dew point and condense into water within the wall; but, if the flow of vapor is impeded by a vapor-resistant material in the wall, the vapor may not reach that point in the wall at which the temperature is low enough to cause condensation. Condensation problems are most frequent during the heating season when buildings of tight, highly insulated construction have occupancies and/or heating systems which produce humidity. This gain in moisture content of the interior air increases the interior vapor pressure substantially above that existing in the outdoor atmosphere. This tends to drive vapor outward from the building through any vapor-porous materials that comprise the wall assembly. This may be controlled either by the use of a properly placed vapor barrier or by decreasing the vapor pressure differential across the wall section through the use of ventilation. Technical Notes 7C contains a discussion of the principles of condensation of water vapor, both on the wall surface and within the wall system. This Technical Notes is devoted to the analysis of wall systems to determine at what point or points in the wall assembly condensation might be expected to occur. EFFECTS OF CONDENSATION Many building materials are affected by water. For example, wood expands with increasing moisture content. If conditions of varying humidity occur in different parts of the cross-section of a single wood framing member, there will be a tendency to warp. High humidity can also cause the decay of wood. Water promotes the corrosion of metal, and many insulating materials show permanent change over the course of time when in contact with water. The insulating value of most materials is greatly reduced by the presence of free water. Volumetric changes in fired clay masonry units due to gains in moisture content are to be expected and should be given consideration in the design process. Alternate freezing and thawing of clay products when saturated may lead to eventual deterioration, such as cracking and spalling. If soluble salts are present in or in contact with brick masonry, moisture caused by condensation may contribute to efflorescence. CONDENSATION ANALYSIS This Technical Notes describes the method used to determine the temperature and vapor pressure gradients of a wall when the exterior and interior design temperatures and relative humidities are known. Accompanying this method is an example of determining the points in a wall system where condensation may be expected to occur. Method The step-by-step method outlined assumes a steady-state heat loss procedure. The wall section and the interior and exterior temperatures and relative humidities are therefore held constant. This procedure is easily adapted to the cooling season by keeping in mind that the temperature and vapor pressure gradients are always plotted across the wall section from the warm side to the cool side. Procedure An 11-column table is set up, similar to that shown in Table 3. The wall components, including the inside air, inside air film and exterior air film, are listed in Column 1. The thermal resistance (deg. F * sq. ft. * hr/Btu) of each wall component is entered in the rows of Column 2 respectively. Values of thermal resistance may be found in Technical Notes 4 Revised, Table 1.
The component thermal resistances are totaled and entered at the bottom of Column 2. The component thermal resistance percentage is calculated by dividing the component thermal resistance by the total thermal resistance of the wall assembly and multiplying this quotient by 100. The results are entered in the rows of Column 3, respectively. Check the total of the component percentages to make sure that they equal 100. The temperature drop across each component is calculated by multiplying the component thermal resistance percentage by the total temperature drop across the wall section (Ti - To), an dividing this product by 100. The results are entered in the rows of Column 4 respectively. A quick check is to total the component temperature drops. They must equal the total temperature drop across the wall section. The temperature of the inside air, Ti, is entered in Row 2 of Column 5. The component temperatures (the temperature of the component's exterior face) are calculated by subtracting the component temperature drop from the temperature of the component preceding it. The results are entered in the rows of Column 5 respectively. Check the calculated temperature of the outside air film. It must equal the temperature of the outside air, To. The component saturated vapor pressures are taken from Table 1 for the temperature of each component, and entered in the rows of Column 6 respectively. The component vapor resistances (in. Hg * sq. ft. * hr/gr), taken from Table 2, are entered in the rows of Column 7 respectively.
In this chapter the permeance, resistance, permeability and resistance per unit thickness values are given in the following units: Permeance Perm= gr/h.ft2.in.Hg Resistance Rep= in.Hg.ft2 h/gr Permeability Perm.in.= gr/h.ft2 (in.Hg/in.) Resistance/unit thicknessRep/in. =(in.Hg.ft2 h/gr)/in. A) Table 2 gives the water vapor transmission rates of some representative materials. The data are provided to permit comparisons of materials; but in the selection of vapor retarder materials, exact values for permeance or permeability should be obtained from the manufacturer of the materials under consideration or secured as a result of laboratory tests. A range of values shown in the table indicate variations among mean values for materials that are similar but of different density, orientation, lot or source. The values are intended for design guidance and should not be used as design or specification data. The compilation is from a number of sources; values from dry-cup and wet-cup methods were usually obtained from investigations using ASTM E96 and C355; values shown under others were obtained from investigations using such techniques as two-temperature, special cell, and air-velocity. Values included were obtained from Ref.14 to 29 and other sources. Some values were obtained from unpublished tests conducted by Pennsylvania State University and the Building Research Div., National Research Council of Canada. B) Depending on construction and direction of vapor flow. C) Usually installed as vapor retarders, although sometimes used as exterior finish and elsewhere near cold side where special considerations are then required for warm side barrier effectiveness. D) Dry-cup method. E) Wet-cup method. F) Other than dry- or wet-cup method. G) Low permeance sheets used as vapor retarders. High permeance used elsewhere in construction. H) Basic weight in lb per 100 ft2 (lb per square ft) I) Resistance and resistance/in. values have been calculated as the reciprocal of the permeance and permeability values. J) Cast at 10 mils wet film thickness.31 K) From ASHRAE Handbook of Fundamentals. The total vapor resistance of the wall section is calculated by totaling the component vapor resistances. This total is entered at the bottom of Column 7. The component vapor resistance percentage is calculated by dividing the component vapor resistance by the total vapor resistance of the wall section and multiplying this quotient by 100. The results are entered in the rows of Column 8 respectively. Check the total of the component vapor resistance percentages to make sure that they equal 100. The actual vapor pressure of the interior and exterior air is calculated by multiplying their saturated vapor pressures by their respective relative humidities. The results are entered in the rows of Column 10 respectively. The total vapor pressure difference is calculated by subtracting the exterior actual vapor pressure from the interior actual vapor pressure. The result is entered at the bottom of Column 9. The component vapor pressure difference is calculated by multiplying the component vapor resistance percentage by the total vapor pressure difference and dividing this product by 100. The result is entered in the rows of Column 9 respectively. Total the component vapor pressure differences. This total must equal the total vapor pressure difference, entered at the bottom of Column 9. The component actual vapor pressure is calculated by subtracting the component vapor pressure difference from the actual vapor pressure of the component preceding it. The results are entered in the rows of Column 10 respectively. The component actual vapor pressures (Column 10) are checked against the component saturated vapor pressures (Column 6). If any wall component has an actual vapor pressure which is larger than its saturated vapor pressure, condensation is likely to occur in that area of the wall section, as indicated by the asterisks in Column 11. Table 3 shows an example of this condensation analysis procedure. The wall being considered is an insulated brick and block cavity wall system. It is assumed that the wall is located in Washington, DC. The analysis is for a winter day with an exterior temperature of 17 deg. F @ 73% relative humidity, and an interior temperature of 72 deg. F @ 50% relative humidity.
1. T.R. Thermal Resistance 2. T.D. Temperature Difference (0F) 3. S.V.P.Saturated Vapor Pressure (in inches Mercury) 4. V.R. Vapor Resistance (in inches Mercury) 5. V.P.D.Vapor Pressure Difference (in inches Mercury) 6. A.V.P.Actual Vapor Pressure (in inches Mercury) 7. Ti Inside Air Temperature (0F) 8. To Outside Air Temperature (0F) 9. RHi Relative Humidity Inside 10. RHo Relative Humidity Outside Notes 1. See Table 1 of Technical Notes 4 Revised. 2. See Table 1 3. See Table 2 4. Condensation is likely to occur in these areas 5. Information Required for this example Ti = 72 To = 17 RHi = 73% RHo = 50% The temperature gradient, as well as the saturated vapor pressure and actual vapor pressure gradients, can be plotted across the wall section, as shown in Figures 2 and 3 respectively. When plotting the saturated and actual vapor pressure gradients, the areas where the actual vapor pressure gradient is above the saturated vapor pressure gradient are where condensation is likely to occur.
Saturated Vapor Pressure Curves FIG. 1
Temperature Gradient FIG. 2
Saturated Vapor Pressure and Actual Vapor Pressure FIG. 3
SUMMARY The analysis procedure presented in this Technical Notes may be used as an indicator of where condensation may occur in a wall section. It may also be used to analyze the effect on condensation potential of varying wall components and vapor barriers. The information contained in this Technical Notes is based on the available data and experience of the technical staff of the Brick Institute of America. This information should be recognized as recommendations and should be used with judgment. Final decisions on the use of the information discussed herein are not within the purview of the Brick Institute of America, and must rest with project owner, designer or both.
Got a technical question about a product? Contact the product specialists at Upchurch Kimbrough Company today online or call 713-957-1520. | ||||||
About Upchurch Kimbrough Creative Applications Special Services Local Portfolio Cost Guide Product Lines Tech Notes Online Resource Request Information Email UKC How to Find Us Home
| ||||||